SKU: 1SAM250000R1013
MS116-20
In stock
₴ 3 706,55
The MS116-20 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 20.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 10 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
Characteristics
Customs Tariff Number
85362010
Brand
ABB Stotz-Kontakt GmbH, ABB Stotz-Kontakt GmbH
Minimum Order Quantity
1 piece
Product Net Weight
0.31 kg
Package Level 1 Units
box 1 piece
Package Level 1 Depth / Length
102 mm
Package Level 1 Height
50 mm
Package Level 1 Width
92 mm
Package Level 1 Gross Weight
0.325 kg
Package Level 2 Units
carton 40 piece
Package Level 2 Depth / Length
395 mm
Package Level 2 Height
210 mm
Package Level 2 Width
280 mm
Package Level 2 Gross Weight
13.386 kg
Declaration of Conformity - CE
1SAD938522-0060
RoHS Information
1SAD938517-0060
RoHS Status
Following EU Directive 2011/65/EU
ETIM 7
EC000074 - Motor protection circuit-breaker
Degree of Protection
Housing IP20/Main Circuit Terminals IP10
Instructions and Manuals
2CDC131011M6802
Dimension Diagram
1SAM200420F0001
Product Net Width
45 mm
Product Net Height
97.8 mm
Product Net Depth / Length
85.4 mm
Setting Range
16 ... 20 A
Rated Operational Voltage
Main Circuit 690 V AC
Rated Operational Current (Ie)
20 A
Rated Frequency (f)
Main Circuit 50 Hz/Main Circuit 60 Hz
Rated Insulation Voltage (Ui)
690 V
Number of Poles
3
Pollution Degree
3
Tightening Torque
Main Circuit 2 N·m
Wire Stripping Length
Main Circuit 10 mm
Recommended Screw Driver
Pozidriv 2
Power Loss
at Rated Operating Conditions per Pole 1.5 W
Standards
IEC/EN 60947-1/IEC/EN 60947-2/IEC/EN 60947-4-1/UL 60947-1/UL 60947-4-1
Ampere Rating UL/CSA
20 A
Tightening Torque UL/CSA
Main Circuit 18 in·lb
Ambient Air Temperature
Around the Enclosure 0 ... +40 °C/Operation -25 ... +70 °C/Operation Compensated -25 ... +55 °C/Storage -50 ... +80 °C
ABS Certificate
1SAA963000-0104
BV Certificate
1SAA963000-0204
CB Certificate
1SAA963005-2003/1SAA963006-2001
CQC Certificate
CQC2011010307506570/CQC2014010307744794
cUL Certificate
cUL_E137861
DNV GL Certificate
1SAA963000-0304
EAC Certificate
1SAA963000-2701
Environmental Information
1SAC200050H0009
GL Certificate
1SAA963000-0402/1SAA963000-0304
LR Certificate
1SAA963000-0505
RMRS Certificate
1SAA918000-0704
UL Certificate
cUL_E137861/UL_E137861
Package Level 1 EAN
4013614405655
Package Level 2 EAN
4013614408731
Object Classification Code
F
ETIM 4
EC000074 - Motor protective circuit-breaker
ETIM 5
EC000074 - Motor protective circuit-breaker
ETIM 6
EC000074 - Motor protection circuit-breaker
eClass
V11.0 : 27370401
UNSPSC
39121521
E-Number (Finland)
3705873
E-Number (Sweden)
3111951
Electrical Durability
50000 cycle
Mechanical Durability
100000 cycle
Terminal Type
Screw Terminals
General Use Rating UL/CSA
(600 V AC) 20 A
DNV Certificate
1SAA963000-0304
KC Certificate
1SAA963000-1501
Horsepower Rating UL/CSA
(200 V AC) Three Phase 5 Hp/(208 V AC) Three Phase 5 Hp/(220 ... 240 V AC) Three Phase 5 Hp/(440 ... 480 V AC) Three Phase 10 Hp/(550 ... 600 V AC) Three Phase 15 Hp
Mounting Position
Position 1 to 6
Actuator Type
Rotary Handle
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715/TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Contact Position Indication
ON / OFF
Full Load Amps Motor Use
(200 V AC) Three Phase 17.5 A/(208 V AC) Three Phase 16.7 A/(220 ... 240 V AC) Three Phase 15.2 A/(440 ... 480 V AC) Three Phase 10 A/(550 ... 600 V AC) Three Phase 15 A
Locked Rotor Amps
(200 V AC) Three Phase 105.8 A/(208 V AC) Three Phase 102 A/(220 ... 240 V AC) Three Phase 92 A/(440 ... 480 V AC) Three Phase 81 A/(550 ... 600 V AC) Three Phase 93 A
Reviews
Description
Brochure
CAD outline drawing
Catalogue
- MS116 / MS132 / MO132 / MS132-T Catalog pages
- 1SBC100195C0203 - Short-form catalog Motor protection and control: Manual motor starters, contactors and overload relays (PDF) - Edition Nov 2016
- 1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition march 2020
Certificate
- CB Certificate - MS116 - Manual Motor Starters
- Gost Certificate - MS116, MS132, MS450, MS451, MS495, MS496, MS497, MO132, MO450, MO495, MO496 - Manual Motor Starters
- Gost Fire Certificate - MS116, MS132, MO132, MS4xx, MO4xx
- RussianRiverRegister Certificate MSxxx, MOxxx
- BV Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starters
- DNV GL Certificate - MS116 - Manual Motor Starter
- LR Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starters
- EAC Certificate - MS116, MS132, MO132, MS165, MO165, HKF1-11 - Manual Motor Starters
- RMRS Certificate - MS116, MS132, MO132, MS165, MO165, MS225, MS325, MO325, MS450, MS451, MS495, MS496, MS497 - Manual Motor Starters
- UL Certificate of Compliance - MS116 & Accessory - Manual Motor Starter
- cUL Certificate - MS325, MS326, MO325, MS225, MS116, MS132, MO132, MO132-K, MS132-T, MS132-K, MS165, MO165 Accessories - Manual Motor Starter
- CQC Certificate, Motor protection circuit breaker, MS116, Made in Germany
- CQC Certificate, Motor protection circuit breaker, MS116, Made in Germany
- ABS Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starter
- KC Certificate MS116
Circuit diagram
Data sheet
- Tripping characteristic - Manual Motor Starter MS116-4.0
- MS116 Manual Motor Starter Data Sheet
- Tripping characteristic - Manual Motor Starter MS116-32
- Tripping characteristic - Manual Motor Starter MS116-25
- Tripping characteristic - Manual Motor Starter MS116-20
- Tripping characteristic - Manual Motor Starter MS116-16
- Tripping characteristic - Manual Motor Starter MS116-12
- Tripping characteristic - Manual Motor Starter MS116-6.3
- Data sheet - Manual Motor Starter MS116 valid for production date from week 29/2019
- Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116
- Cut-off Current Characteristic @ 500V -Manual Motor Starter MS116
- Tripping characteristic - Manual Motor Starter MS116-10
- Cut-off Current Characteristic @ 690V -Manual Motor Starter MS116
- I2t - Characteristic @ 500V - Manual Motor Starter MS116
- Tripping characteristic - Manual Motor Starter MS116-2.5 valid for production date from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-1.6 valid for production date from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-1.0 valid for production date from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-0.63 valid for production date from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-0.40 valid for productiondate from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-0.25 valid for production date from week 34/2014
- Tripping characteristic - Manual Motor Starter MS116-0.16 valid for production date from week 34/2014
- I2t - Characteristic @ 690V - Manual Motor Starter MS116
- I2t - Characteristic @ 400V - Manual Motor Starter MS116
Declaration of conformity
- CCC Declaration of Conformity, Motor protection circuit breaker, MS116, Made in Germany
- EU Declaration of Conformity - MS116, HK1, SK1, HKF1, UA1, AA1, IB132, DMS132, MSHx, FS116, OXS, MSMN, MSAH1, BEMC, S1-Mx, PB1, PS-1 - Manual Motor Starter
- UK Declaration of Conformity - MS116, HK1, SK1, HKF1, UA1, AA1, IB132, DMS132, MSHx, FS116, OXS, MSMN, MSAH1, BEMC, S1-Mx, PB1, PS-1 - Manual Motor Starter
- Declaration of Conformity MS116
- CCC Declaration of Conformity, Motor protection circuit breaker, MS116, MS2X, Made in China
- CCC Declaration of Conformity, Motor protection circuit breaker, MS116, Made in Germany
Drawing
- Dimension Drawing - MS116 (<20A) + HK1/SK1 Manual Motor Starter
- MS116 + BEA16/116 + A9 ... A16
- MS116 + BEA16/116 + 2 x A9...A16 + VM/VE5-1 + BER16..+ PM26-23
- MS116 + BEA16/116 + 2 x A9...A16 + VM/VE5-1 + BER16..+ PM26-23
- MS116 + BEA16/116 + 2 x A9...A16 + VM/VE5-1 + BER16..+ PM26-23
- MS116 + BEA26/116 + 2 x A26 + BER40.. + PM26-23
- MS116 + BEA26/116 + 2 x A26 + BER40.. + PM26-23
- MS116 + BEA26/116 + 2 x A26 + BER40.. + PM26-23
- Dimension Drawing - MS116 (<20A) + UA1/AA1 Manual Motor Starter
- Dimension Drawing - MS116 (<20A) + HKF1 Manual Motor Starter
- Dimension Drawing - MS116 (20A) + HKF1 Manual Motor Starter
Environmental product declaration
Leaflet
Manual
Operating instruction
Reviews
There are no reviews yet.



There are no reviews yet.